150℃ / 180℃ Water temperature control unit (LEWH/LEWT Series)
About the unit The water temperature controller LEWH/LEWT series is designed to work with a wide range of high temperature application up to 150/180 ºC, which are used for controlled heating of products, mechanisms and factory machinery in a wide range of industries, including chemical reaction and casting industry etc.
High temperature water from the mould is returned to the unit and pressurized by high-pressure pump, sent to the heating tank and finally to the mould with a constant temperature. |
![]() |
![]() |
Main specification Temperature rage: Inlet water temp +15℃~180℃ |
Feature
- High precision ±1°C controlled
- Return water temperature display
- Explosion proof design for pipeline
- Stainless steel pipeline reduce resistance and rusty
- Omron, Fuji, LG, Siemens, Schneider brand electrical equipment
- Microcomputer control system
- Automatic exhaust function for start-up
- Heating power switching function
- Improved safe protection and fault indication, easy operation for maintenance
- Isolated type electric control box prolong the service life of electric appliance
- By-pass pressure relief loop
Availably option
- Instant cooling and shut-down function
- Multi-point temperature control unit can be customized
- RS 485 communication function for remote control
- PLC control system and touch screen
Safety protection function
- Abnormal temperature protection
- Reverse phase protection of power supply
- Short circuit protection
- Pump overload protection
- Water shortage protection
- Abnormal heating protection
- Pipe clogging protection
- Abnormal pressure stops heating protection
- Automatic exhaust protection
Application: |
|
|
|
Specification sheet
Model | Unit | LEWH-10 | LEWH-20 | LEWH-30 | LEWT-10 | LEWT-20 | LEWT-30 | |
Temp. control range | ºC | Inlet water temperature +15-150ºC | Inlet water temperature +15-180ºC | |||||
Temp. control accuracy | PID±1ºC | |||||||
Power supply | AC3Φ380V 50HZ 3P+E(5M) | |||||||
Heat transfer medium | Water | |||||||
Cooling methad | Indirect cooling | |||||||
Heating capacity | KW | 9 | 12 | 24 | 9 | 12 | 24 | |
Pump power | HP | 1 | 2 | 3 | 1 | 2 | 3 | |
Max.pump flow | L/min | 95 | 153 | 235 | 95 | 153 | 235 | |
Max.pump pressure | Bar | 6 | 6 | 6 | 12 | 12 | 12 | |
Total power | KW | 10 | 14 | 26 | 12 | 14 | 26 | |
Cooling water pipe | Inch | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | |
Circulation water pipe | Inch | 3/8*4 | 3/8*4 | 3/8*4 | 3/8*4 | 3/8*4 | 3/8*4 | |
Dimension | L | 780 | 780 | 1100 | 780 | 780 | 1100 | |
W | 360 | 360 | 420 | 360 | 360 | 420 | ||
H | 880 | 880 | 1100 | 880 | 880 | 1100 | ||
Weight | kg | 75 | 85 | 95 | 75 | 85 | 95 |
Note: The specification is subject to change due to product improvement without prior notice.